Share:


OMX 211PM DIGITAL CONVERTER



The OMX 200 model series are digital DIN rail mounted signal converters housed in an enclosure only 12.5 mm wide.

The OMX 211PM type is a simple single-channel isolator with a convenient setting of the input and output ranges either using a DIP switch on the side of the housing or the free OM Link SW from a PC.
This device is based on a microprocessor with a 24-bit ∆∑ A/D converter, which guarantees high accuracy and excellent stability.
 

  • Input: 0…2/5/10 V
    0…5/20 mA, 4…20 mA, passive/active

  • Analogue output, passive/active

  • Quick configuration by DIP switch

  • PC configurable via USB port

  • Galvanic isolation 2.5 kVAC

  • Simple instalation to DIN rail

  • Power supply 10…30 VDC, 24 VAC



    Technical Data:

    Input
    *
    Number of inputs
    1 input
    PM
    Range
    0…5 mA
    < 200 mV
    0…20 mA
    < 200 mV
    4…20 mA
    < 200 mV
    ±2 V
    1 MOhm
    ±5 V
    1 MOhm
    ±10 V
    1 MOhm
    Projection
    Signalizing LED
    PWR, SET Device status signaling (RGB)
    Settings
    Control
    The device is controlled and set by a single button on the front panel
    OM Link
    Company communication interface for operation, setting and update of device firmware (microUSB)
    OM Link program is also designed for visualization and filing of meas. values from more instruments
    Instrument accuracy and functionality
    Temperature coefficient
    15 ppm/°C
    Accuracy
    ±0,1 % z rozsahu (pro 20 mΔ›ření/s)
    Rate
    1…100 measur./s
    Overload capacity
    2x; 10x (t < 30 ms)
    Linearization
    lineární interpolací v 100 bodech (pouze přes OM Link)
    Digital filters
    arithmetic mean from 2…100 measurements
    floating mean from 2…30 measurements
    exponential mean from 2…100 measurements
    zaokrouhlení nastavení pevného kroku pro zmΔ›nu hodnoty
    Functions
    Tare designed to reset display on non-zero input signal
    Min/max value registration of min./max. value achieved during measurement
    Teach-in semiautomatic regime of input calibration
    Simulace simulace vstupního signálu/funkce přístroje
    Math. functions
    polynom, invertní polynom, logarithm, exponential, power, root
    Watch-dog
    reset after 500 ms
    Calibration
    at 25°C and 40 % r.h.
    Analogue outputs
    Number of outputs
    2 outputs
    Type
    Isolated, programmable with resolution of max.10,000 steps, type and range are menu selectable
    Temperature coefficient
    15 ppm/°C
    Nonlinearity
    ±0,1 % of range
    Rate
    response to value change < 160 µs
    Ranges
    0…10 V / 10...0 V (resistive load > 2.6 kOhm), 0...20 mA, 4…20 mA / 20...4 mA (aktivní/pasivní)
    Compensation
    600 Ohm/12 V
    Error state
    error message indication (<3.0 mA)
    Sensor excitation
    Fixed
    24 VDC/35 mA, isolate (only for 4...20mA)
    Power supply
    Power supply
    10…30 VDC/24 VAC, ±10 %, PF > 0,4, I < 40 A/1 ms, isolated
    Current draw
    < 2,4 W/2,6 VA
    Power supply protection
    Power supply is protected by a fuse inside the instrument
    Operating conditions
    Connection
    connector terminal board, cable section < 2,5 mm2
    Stabilization period
    within 5 minutes after switch on
    Operating temperature
    -20°…60°C
    Storage temperature
    -20°…85°C
    Protection class
    IP20
    El. safety
    EN 61010-1, A2
    Dielectric strength
    2,5 kVAC within 1 min. between pow. supply and input
    2,5 kVAC po 1 min. mezi vstupem a výstupem
    2,5 kVAC within 1 min. between output
    Insulation resistance
    for polution degree II, measuring cat. III.
    napájení přístroje 300 V (ZI), 255 V (DI)
    input, output 300 V (ZI)*
    EMC
    EN61326-1: 2006
    Seismic capacity
    IEC/IEEE 60980-344 ed. 1.0:2020, par 6,9
    Mechanical durability
     

     

    Mechanical properties
    Material
    PA 66, non-inflammable UL 94 V-0 (black)
    Dimensions
    114,5 x 99 x 12,5 mm (w x h x d)
     



 Inquiry - OMX 211PM DIGITAL CONVERTER